养老院不应设置在地下或半地下。
1, should not be installed in the underground or semi-underground nursing home.
2、养老院采用三级耐火等级的建筑时,不应超过二层;采用四级耐火等级的建筑时,应为单层;设置在三级耐火等级的建筑内时,应布置在首层或二层;设置在四级耐火等级建筑内时,应布置在首层。
2, nursing homes using class refractory buildings, shall not be
more than 2; Using level 4 fireproof rank construction, should be
single; Set in the class refractory buildings, should be arranged in the
first or second; Set in the four levels of refractory grade buildings,
should be decorated on the first floor.
3、养老院相邻护理单元之间应采用防火隔墙分隔,隔墙上的门应采用乙级防火门,设置在走道上的防火门应采用常开防火门。
3, between adjacent nursing home care unit should use fire
partition separating, partition door should be adopted in serie b fire
doors, fire doors should be set in a hallway with normally open fire
door.
4、疏散楼
泵梯不得少于两个,养老院的疏散尽量采用环形走道和外廊设计。
4, ladders shall not be less than two, the evacuation of nursing
home USES annular walkway and side corridor design as far as possible.
5、失能或半失能的老年人应优先安排在便于疏散的地点。
5, disability, or disability of the elderly should be prioritized in the location of the evacuation